title: Socomec UPS Device: Power source for output phases
agents: snmp
catalog: hw/power/socomec
license: GPL
distribution: check_mk
description:
 Checks by which source the output phase is powered. Warns if the device
 reports internal maintenance bypass or bypass, goes critical during battery operation
 ({"On inverter"}) or when offline. Caveat: Currently, states are interpreted according to
 the NetVision-nv6 MIB. Other firmware versions might be incompatible. Please send us a
 {cmk --snmpwalk} along with a description as to how the check behaves unexpectedly in
 your setup.

inventory:
 One check per Socomec UPS is created.